Time relay is a kind of automatic switch device which realizes delay control by electromagnetic principle or mechanical principle. When the input action signal is added (or removed), the output circuit needs to undergo a specified precise time to produce a jump change (or contact action) relay. It is an electrical component used in a lower voltage or lower current circuit to switch on or off a higher voltage or larger current circuit. At the same time, the time relay is also a control appliance that uses electromagnetic principle or mechanical principle to achieve delay control. There are many kinds of it, there are air damping, electric and electronic type.

Time relay is a kind of control electrical apparatus which realizes delay control by electromagnetic principle or mechanical principle. There are many kinds of it, there are air damping type, electric type and electronic type and other types.

Product characteristics:

1, the air damping type time relay is also known as the air bag type time relay, it is based on the resistance of air compression to delay, its structure is simple, cheap, delay range is large (0.4~180s), but the delay accuracy is low.

2, electromagnetic time relay delay time is short (0.3~1.6s), but its structure is relatively simple, usually used in power delay occasions and direct current circuit.

3, the principle of the electric time relay is similar to the clock, it is driven by the internal motor to rotate the reduction gear and obtain the delay. This relay delay accuracy is high, the delay range is wide (0.4~72h), but the structure is more complex, the price is very expensive.

4, transistor type time relay is also known as electronic time relay, it is the use of delay circuit to delay. This kind of relay has high precision and small size.

Time relay can be divided into power delay type and power delay type two types:

Take air damped time relay as an example to explain the working principle of time relay Air damped time relay delay range (0.4-60s and 0.4-180s two kinds) It is simple in structure, but the accuracy is low.

When the coil is energized, the armature and the support plate are attracted by the core and move down instantaneously, making the instantaneous action contact open or open. However, the piston rod and lever can not fall with the armature at the same time, because the upper end of the piston rod is connected to the rubber film in the air chamber, when the piston rod begins to move downward under the action of the release spring, the rubber film is concave, and the air in the air chamber above becomes thin and the piston rod is damped slowly. After a certain time, the piston rod drops to a certain position, and the delayed contact action is pushed through the lever, so that the dynamic break contact is disconnected and the dynamic close contact is closed. From the winding power to the completion of the delay contact action, this time is the delay time of the relay. The length of the delay time can be changed by adjusting the size of the air inlet in the air chamber with screws.

After the suction coil is powered off, the relay is restored by the action of the recovery spring. The air is rapidly discharged through the vent hole.

Time relay: When adding or removing the input signal, the output part needs to delay or limit the time to close or disconnect its controlled line relay.